Multi-line 300 PPU 300 ver. 1.x.x.

Multi-line 300 PPU 300 ver. 1.x.x.

You have chosen to download our software.

Within a few seconds, you will receive an email containing a download link.

Having trouble using the software? Please contact support@deif.com. 

Best regards, 

DEIF A/S

The software is subject to copyright DEIF A/S
By following the above mentioned link and downloading the file you automatically accept DEIF A/S copyright and license agreement (EULA). The license agreement can be found on www.deif.com/software

1.0.26.3

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.19.0

PPU 300

Changes:

• Fixed issue where the controller crashed creating a backup.

1.0.26.2

24/12/2023

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.19.0

PPU 300

Changes:

• Updated CODESYS libraries.

1.0.26.1

11/12/2023

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.19.0

PPU 300

Corrections:

• Optimised CPU performance.
• Fixed issue where engine cooldown was not stopped when changed to switchboard control.

1.0.26.0

07/12/2023

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.19.0

PPU 300

New features:

• Added emergency stop alarm to the parameter list.
• Added "Three-phase UL1L2 & IL1" as a new wiring mode option in the AC configuration.

Corrections:

• Corrected an issue where it was possible to override an application output from Modbus.
• Corrected an issue where the controller performed an unwanted restart due to an uncommon issue in Modbus.
• Corrected an issue where reading the IO status on Modbus could cause an unwanted restart of the application software.
• Corrected an issue where digital outputs stayed high after removing the configuration.

1.0.21.1

29/03/2023

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.19.0

PPU 300

Corrections:

1 - Fixed issue where the voltage offset in reactive power load share did not react

1.0.21.0

21/10/2022

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.19.0

PPU 300

New feature:

1 - Added support for multiple applications with a parameter to select active application and custom plant name. (Not supported by PICUS yet.)
2 - Added possibility to adjust frequency offset for power load share regulating.

Corrections:

1 - Fixed bug where SC does not close, because sync. never finishes in emulation.
2 - Fixed issue where "Ramping to xx" was stuck in status text.
3 - Fixed issue where IO parameter configuration was passed on from one external breaker or a heavy consumer on the single line to another during commissioning. IO configuration and parameters are not reset.
4 - Fixed issue where engine ready delay was ignored before regulation.
5 - Fixed issue where manual regulation didn't work in emulation.
6 - Fixed issue where analogue regulation was unstable in emulation.
7 - Fixed issue with GAM3.2 not working in emulation.
8 - Actual power total in % is now showing on DU-300 (Live data) and in PICUS.

1.0.20.0

20/07/2022

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.19.0

PPU 300

New feature:

  • Added Aftertreatment dashboard
  • Added possibility to create custom popups from CODESYS
  • Added possibility to set custom status text from CODESYS
  • Custom counters added to CODESYS and Customlogic
  • Added possibility to setup power transformer on genset and hybrid controllers

Changes:

  • Backup of eventlog changed to get latest 1000 events.
  • Corrected min, max and default value for AVR relay output Maximum ON time

Corrections:

  • ACM3.1 card will not start protections if settings is lost during operation. A power cycle of the controller will be required to restart the protections. Alarm ""ACM protection not running"" will be shown continuously if the problem occur.
  • Fix the issue there EDG only have 1 set of synchronization settings
  • Fixed - Reboot of controllers required after SW update
  • Fixed issue where AC protections could change "AC setup" after power cycle of the controller
  • Fixed issue where is not possible to stop SC or SG in emulation, if the breaker was closed
  • When synchronising using static sync. The GOV and AVR on the syncing controller should no longer give spikes when a blackout happens on busbar.

DU 300:

New features:

  • Introduces a new view for exhaust after-treatment dashboard increasing the support of Tier 4 and Stage V engines.

 

1.0.18.0

23/04/2022

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.18.0

Minimum required version of PICUS: 1.0.18.0

PPU 300

New feature:

  • Added custom alarms in CODESYS
  • Added possibility to disable display buttons in individual groups
  • Added control signal to engine communication + extra protocols
  • Reset horn is possible to reset with input

Corrections:

  • Action for the synchronization failure alarm is now visible in PICUS and DU.
  • Fixed issue where counters does not work in Custom Logic
  • Fixed issue where synchronize indicator on display is visible with dead busbars
  • Fixed issue with alarm test, does not work when alarm state was unacknowledged no alarm
  • Fixed problem where Picus would show empty Application or I/O status page.
  • Fixed issue where measurement averaging has causing a very small offset the the averaged measurement.
  • Fixed issue where emulated values was slower when using measurement averaging.
  • Fixed issue where the additional logged values in the event log could be incorrect when measurement average is used.

DU 300:

New features:

  • DU300 button management.
    • Added the ability to disable (and enable) the buttons of the DU300 by parameters.
    • The buttons are disabled in blocks related to their functionality.
    • This provides more possibilities to configure the controller to the application's requirements.

Corrections:

  • Fixed an issue with the differentiation of two synchroscopes with the same measurements, like an EDG.
  • Fixed an issue related to ANSI codes shown on the alarm popup.

1.0.17.0

10/02/2022

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.17.0

PPU 300

New Features:

  • For CODESYS application it is now possible to have a function block for special hardware, without having the hardware.

Corrections:

  • Changed the maximum value for Breaker close failure delay to 30 seconds.
  • Changed the maximum value for Breaker Pulse ON time to 60 seconds.

DU 300

Changes:

  • Improved navigation and look of the Parameters page.

Corrections:

  • Solved an issue that would cause the DU 300 to crash when downgrading DU software.

1.0.16.0

13/10/2021

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.16.0

PPU 300

New Features:

  • Added ANSI code tag to relevant alarms
  • Added possibility for disabling Ethernet ports
  • Added REST version to version page
  • Change the behavior of "Update" input for custom parameters in CODESYS
  • Added any functionality to ICC flags
  • Increase number of ICC flags to 32

Corrections:

  • Fixed issue where GAM3.2 stand alone was active when regulator was set "OFF"
  • Fixed issue in CODESYS where custom parameters write FB not working after read FB has been called

DU 300

New Features:

  • Support for Tags:
    • New menu for options to display the tags set in parameters.
    • Options for tag visualisation include: Alarm pop-up, alarm list, logs page and parameter page.

Changes:

  • Update to languages
  • Connection improvements

Corrections:

  • Solves an issue where the display could enter a manual loop after returning from synchroscope.

1.0.15.0

12/07/2021

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.15.1

PPU 300

New Features:

  • CPU load is now accessible and displayed through the performance widget.
  • Change of counters is added to the event log.
  • CPU load is now a measurement shown as a Live data value or a Modbus address, and it is accessible as an Analogue Output.
  • New counters relating to engine/inverter starts are added.
  • New counters relating to breaker operations are added.
  • Energy import and difference counters are added to hybrid.
  • External breaker states are added to CustomLogic.

Changes:

  • Counters are now specifically signed or un-signed.
  • Text on Live data screen is changed for Engine speed.
  • CustomLogic bit outputs are now reset to 0, and then deleted from the configuration.

Corrections:

  • Corrected that "Different power management rules activate" alarm was triggered incorrectly.
  • Corrected the behaviour of Continuous breaker.
  • Corrected missing paths for Modbus "Inhibited" flags.
  • Corrected an issue where the display would jump to sync. view if a trip alarm occurred.
  • Corrected an issue where "ball" on the synchronization view could change between red and green, when the breaker was closed.
  • Corrected an issue where the alarm counter did not increment if the state was not State A – Normal.
  • Corrected an issue where a Stand-alone EDG would not deload the GB in SEMI-AUTO mode.
  • Corrected an issue where the scale "(4 to 20mA) to (0 to 100%)" displayed 4.0mA instead of 0.0mA on GAM3.1.

DU 300

Changes:

  • Font size and duration of error message increased in the virtual keyboard.
  • New counters icon for alignment with PICUS.

Corrections:

  • "Missing" counters removed from the display.
  • Units shown for the I/O terminals.
  • Counters are now limited based on the counter type.
  • Display restarts on I/O pages when fieldbus configuration is updated.
  • LED's no longer light up before the screens become active.
  • Passwords with special characters can now be used from the display.

1.0.14.1

01/06/2021

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.15.0

PPU 300

Corrections:

  • Allows IOM3.4 Firmware revision 1.0.0.2.

DU 300

New features:

  • Synchroscope view.

Changes:

  • Local display configurations (for example, brightness and units) will now be kept when new application software is installed.

Corrections:

  • Bar graphs and gauges animations performance is increased.
  • Fixed an issue in View Design where up/down keys lost focus after a blue pop-up.
  • Fixed an issue in Parameters where up/down buttons would not be shown.

1.0.14.0

21/05/2021

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.15.0

PPU 300:

New feature:

  • Emulation feature is added.
  • It is now possible to open the breaker when there is a position failure.
  • All I/O cards and CAN bus values can now be mapped in Modbus.
  • ECU: Communication failure is added. When communication is expected, but not present, an alarm is triggered.
  • Live data: J1939 protocol is now available for engine communication.
  • An option for customers to add CODESYS application version to the version page is added.
  • Idle run start is added.
  • Idle run stop is added.
  • Inhibit for idle run is added.
  • It is possible to skip Idle Run Stop by requesting "Stop" again.
  • It is possible to skip Idle Run Start by requesting "Start" again.
  • CODESYS inputs and outputs are available in Modbus.
  • CustomLogic inputs and outputs (digital and analogue) are available in Modbus.
  • Inhibit status for alarms is available in Modbus.
  • Alarm property "Remove from service" is now available in Modbus.
  • The external regulation value can now be read in the regulator status tool.
  • State of the manual regulation input can now be read in the regulator status tool.
  • The source of regulation can now be read in regulator status tool.
  • Engine ECU: Process data alarms are added, and it is now possible to get application alarms from either the ECU or an analogue input.
  • Engine ECU data has been mapped to communication (incl. standard Modbus) and is configurable in flexible Modbus.
  • New ECU: Auto discover is added and can be activated from either CustomLogic, CODESYS, Modbus, or Commands.
  • Live data groupings are arranged in groups according to the engine sub systems.
  • Live data screen view: Now you can see measurements from different sources based on the priority Analogue/IO over ECU.

Changes:

  • The Modbus connections for Idle Time Expired are changed from 100 seconds to 10 seconds.
  • The default AC setup values are changed.
  • "AVR trip" location in CustomLogic for Hybrid is cleaned up.
  • The text for Hybrid is corrected.
  • Spelling error: "Deloading" is changed to "De-loading".
  • Phase sequence error text is corrected for Hybrid.
  • Default settings for blackout detection mismatch alarm are changed.

Correction:

  • Fixed that Modbus crashed when trying to connect many times, and not getting a new connection.
  • Fixed an issue with continuous breaker with mismatch between closing failure and output states.
  • Breaker operation counter increment is now working.
  • Load sharing miscalculation for SG is corrected.
  • Trip counter is now incremented for Hybrid when a trip occurs.
  • Shore and shaft supervision status is fixed.
  • Fixed an issue where default max value for EIM3.1 resistance analogue input sensor was to high.

DU 300

New features:

  • Synchroscope view.

Changes:

  • Local display configurations (for example, brightness and units) will now be kept when new application software is installed.

Corrections:

  • Bar graphs and gauges animations performance is increased.
  • Fixed an issue in View Design where up/down keys lost focus after a blue pop-up.
  • Fixed an issue in Parameters where up/down buttons would not be shown.

1.0.13.2

14/04/2021

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.15.0

PPU 300:

Correction:

  • Fixed issue where controller restarts if writing to oil pressure on Modbus
  • Included bugfix on EIM3.1

DU 300

New features:

  • Synchroscope view.

Changes:

  • Local display configurations (for example, brightness and units) will now be kept when new application software is installed.

Corrections:

  • Bar graphs and gauges animations performance is increased.
  • Fixed an issue in View Design where up/down keys lost focus after a blue pop-up.
  • Fixed an issue in Parameters where up/down buttons would not be shown.

1.0.13.1

24/02/2021

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.15.0

PPU 300:

Corrections:

  • Fixed an issue where the link status of a CODESYS digital output was not correct after download/restore.

DU 300:

New features:

  • Synchroscope view.

Changes:

  • Local display configurations (for example, brightness and units) will now be kept when new application software is installed.

Corrections:

  • Bar graphs and gauges animations performance is increased.
  • Fixed an issue in View Design where up/down keys lost focus after a blue pop-up.
  • Fixed an issue in Parameters where up/down buttons would not be shown.

1.0.13.0

16/02/2021

Versioning changed for alignment within platform.

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.14.0

PPU 300:

New features:

  • AC measurement averaging:
    • It is now possible to use averaging filters (200ms and 800ms) to reduce the value fluctuations from the high performance of the measurement cards.
    • The averaging filter can be applied selectively to different types of measurements.
    • AC measurement averaging affects data displayed by DU 300, PICUS, trending, CustomLogic, CODESYS, and Modbus.
    • AC measurement averaging does not affect protections and regulation values.
  • EIM3.1 Safety shutdown function:
    • EIM3.1 can now be used as a safety shutdown module.
    • EIM 3.1 will be able to run the engine in stand-alone mode should it no longer be able to communicate with the main processor card (PCM).
  • Hybrid controller type added.
  • Support of electronic engines protocols (EIC):
  • Supports the Generic J1939 protocol for reading.
  • J1939 values, alarms and historical events are now available.
  • New engine measurement inputs + alarms added for: Oil pressure, Oil temperature, Coolant temperature, and Coolant level.
  • Flexible application drawing:
    • It is now possible to customise the application drawings to provide a customisable interface.
    • The design of applications with multiple ring connections is now supported.
  • CODESYS version information:
    • It is now possible to readout CODESYS versions in PICUS in the information tab.
    • It is now possible to readout if the licence key is active or not.
    • It is now possible to readout what type of license is active.
  • CustomLogic IO added to Flexible Modbus

Changes:

  • Update rate of live data in display and PICUS is increased.
  • Changed: Possible to change time and date individually from PICUS.
  • The password length can now be 1 to 32 characters.
  • New default password is "0" for all users.
  • Controller type can now be changed during backup restoration.
  • Changed parameter menu structure for Cos Phi set point. Set point, offset and limit.
  • When changing single-line diagram - cleaning up alarms related to redundant breaker.


Corrections:

  • Issue fixed where breaker opened before breaker open point is reached.
  • Fixed issue where hidden Modbus addresses was accessible.
  • Fixed issue where NELs trip if breaker is opened.
  • Fixed issue with rounding problems on decimal values on Modbus data.
  • Fixed issue where changing of counters from Modbus not was saved if there was a controller power cycle shortly after.
  • Fixed issue where remote and local LEDs both were turned on.
  • Fixed issue with unsupported functions in CODESYS libraries.
  • Fixed issue where trip output does not activate when "breaker position failure" is active.
  • Fixed issues where custom parameters in CODESYS stop working after multiple downloads of CODESYS application.
  • Fixed rare issue where backup file was corrupted.
  • Fixed issue where custom alarms do not get units in the alarm and event logs.
  • Fixed issue where GAM3.2 stand-alone mode does not work with PWM output.
  • Fixed issue where regulator did not reset on external stop.
  • Fixed issue where extended stop delay was skipped on external stop.
  • Alarm timer expired flag data added to Modbus.
  • Fixed issue where BTB was not deloaded by DG.
  • Fixed issue where different controller software will run in same system.
  • Fixed issue where breaker open signal could be sent because of missing inhibit info on ACM3.2.
  • Fixed issue where AMC3.2 protections did not work on the Shaft generator.

DU 300:

New features:

  • Custom alarm action suppression: It is now possible to enable alarm suppression for custom alarms from the display.
  • Fast data interface: Faster update rate of gauges, counters, status texts, and live data views.
  • Engine communication:
    • J1939 alarms and historical events.
    • Fieldbus, configuration, supervision and CANbus error handling.

Corrections:

  • Fixed translation of texts in the View designer.
  • Fixed translation of message box popup breadcrumb.
  • Fixed DU300 live data subheader text cutting lower case p, g, j, q, y letters.
  • Fixed DU300 showing negative ampere.
  • Fixed conversion between C and F not having effect on scaling (View design).

1.0.7.0

09/06/2020

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.11.0

PPU 300:

New features:

  • Support for the new IOM3.2 and IOM3.3 cards.
  • Derate of nominal power is now possible with an analogue input.

Correction:

  • Fixed an issue where PICUS supervision would update if the regulator type was changed.
  • Fixed an issue where EIM3.1 relay 4 wire breaker supervision was not working.
  • Fixed an issue where IOM3.4 custom texts could be mixed up if more than one card were used. This fix result in a break of backward compatibility, if custom text has been used on IOM3.4 cards.
  • Fixed an issue where adding a previously used extension rack to a new system could cause the controller to restart.
  • Fixed an issue where connection to an extension unit could cause the controller to restart in a system with more than two extension units.

DU 300:

New features:

  • Support of IOM3.2 and IOM3.3.

1.0.5.0

17/12/2019

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.11.0

PPU 300

New features:

  • Fixed that the display couldn't show negative values on graphs.
  • Live data screens can now be configured by the user.
  • Enhanced Backup/Restore: Restoring of CODESYS is now optional.
  • Fixed that the alarm "Different single-line diagram" would trigger during broadcast of a single-line.
  • Continous breaker: Configuration requiring only one output is now possible.
  • "Fast overcurrent" now has configurable max. range.
  • Breaker feedback: Configuration requiring only one input for feedback is now possible.
  • Support for Network Time Protocol (NTP).
  • Command sources: Setting of permissions for each individual Local/Remote source (PICUS, Display, Modbus, I/O or CustomLogic) is now possible.
  • Alarms can now be tested individually.
  • Support for ACM3.2 card.
  • Modbus: Registers for alarm trip value is now available.
  • Alarm "Inverse time overcurrent": Threshold is now configurable.
  • Redundant breaker feedback is now possible.
  • Spring loaded breaker: Arming of spring is now possible via input.
  • Breaker tripping and opening can now be assigned to individual outputs.
  • AVR can now be tripped by specific alarm actions.
  • Single line: Support for 32 controllers.
  • Flexible Modbus: User configuration of register mapping and support for additional servers.
  • Alarm details now include number of times the alarm was triggered.
  • Nominal settings: 4 sets are now available.
  • User interfaces: Different languages are now supported.
  • Modbus: Registers for Date/Time are now available.
  • Configurable alive/watchdog functionallity is now available.
  • IO Extension units: This feature allows expansion of a ML 300 system with additional decentralized racks containing the desired I/O cards.
  • Firmware update: Replacement cards can be updated without using the utility software
  • Firmware upgrade: In case of controller not beeing ready for update, detailed information about cause is now shown.
  • CODESYS: Improved I/O response time.

Changes:

  • Fixed that name of parameter group "Power supply" in relation to "EIM" was misleading. Moved to the "Hardware" section.
  • Fixed that naming of GAM3.2 I/O's did not comply with naming of other I/O's.
  • Fixed that GOV and AVR parameters did not use the same layout.
  • Minimum OK frequency minimum value and Minimum OK voltage changed to 70 %.
  • Not possible to set inhibits on "System not OK" alarm.

Corrections:

  • Fixed that software version check was only made on the first card in a rack.
  • Fixed that configurable I/O's could maintain their state after beeing unconfigured.
  • Fixed that alarm actions not allowed for a given controller type could be selected anyway.
  • Fixed that event "Start enabled deactivated" could register, even if conditions were not met.
  • Fixed that alarms for "Power import" were missing on BTB.
  • Fixed that changing the calculation method for "Q nominal" would not reflect on the HMI custom view.
  • Fixed general error in sync check.
  • Fixed that some labels in the PICUS menu hierarchy would be truncated.
  • Fixed that BTB blackout close would display the wrong pop-up text ("Busbar A voltage/frequency not OK").
  • Fixed that removing input function from an Analogue output did not reset the Analogue output to "0".
  • Fixed that Active/Reactive power differential counter pulse functionallity did not activate when importing power, only when exporting.
  • Fixed that "Running hour counters" were missing in CustomLogic.
  • Fixed that inhibit "ACM wirebreak" did not reflect the correct state.
  • Fixed that in an engine stop sequence during "Crank off time", if a "Stop command" was issued and the engine had already stopped, the "Crank off timer" was not aborted.
  • Fixed that alarms for P and Q load sharing failure were active during load share ramp-up.
  • Fixed that regulation delay for GOV and AVR was ignored during engine start.
  • Fixed that GOV and AVR regulation would continue during engine stop sequence.
  • Fixed that "Power derate" would wrongly also affect "Breaker open point".
  • Fixed that the alarm "Close failure" on a "Compact breaker" would trigger prematurely.
  • Fixed that some engine states were not available in CustomLogic.
  • Fixed that regulation delay for GOV and AVR was ignored during engine start.
  • Fixed that alarms for "Phase sequence error" were reversed with regards to A/B side.
  • Fixed that requesting "Reset to offset" on GOV or AVR regulator would result in output values not matching the setting in parameters "GOV/AVR output offset".
  • Fixed that the triggered value in alarm details would not be updated if an alarm was re-triggered.
  • Fixed non-responsive Modbus commands related to breaker operations.
  • Fixed the default parameter values for Ti, GOV and AVR manual regulator.
  • Fixed that AVR regulator mode "Fixed Voltage" did not "freeze" the regulator output, when the system lost one or more of the AC measurements.
  • Fixed that alarms with fail class "Block" would not abort the synchronize sequence.
  • Fixed that "SI-unit" label was repeated on some parameters settings.
  • Fixed that digital inputs were unavailable in CustomLogic.
  • Fixed that on the Supervision screen in PICUS the actual state of the busbar and the color representing it would mismatch.
  • Fixed that the alarm "Redundancy broken" had wrong trigger conditions.
  • Fixed that the alarm "Protection set point out of range" had wrong trigger conditions.
  • Fixed that "GAM3.2 status OK" was available as I/O source in PICUS, even when GAM3.2 was not part of the controller configuration.
  • Fixed that the pop-up message "Breaker close cancelled" did not show when conditions were in fact met.
  • Fixed that "Power derate curve" was limited to a max. setting of 200. Increased to 1000.
  • Fixed that "Derate" functionallity did not use the same base for "Power Available" calculation in [%] and in [kW], thus resulting in conflicting values.
  • Fixed that if a blackout is detected (real or loss of measurements) during the synchronisation part of a close sequence the sequence would be cancelled.
  • Fixed that supervision of SCs in PICUS would show shore measurements where ship measurements were supposed to be shown.
  • Fixed that the Backup and Restore action buttons after a restore were no longer shown in the PICUS menu.
  • Fixed that the alarm "Inverse time over-current" were not available for use on "Outputs".
  • Fixed that alarm "Busbar Phase sequence error" was unavailable in CustomLogic and Outputs.
  • Fixed that certain Modbus addresses could not be used as commands.
  • Fixed that "Operations counter" did not work for external breakers.
  • Fixed that "Acknowledge alarms" in combination with the "Alarm TEST" functionallity could result in a controller restart.
  • Fixed that CustomLogic ICC flags could become unavailable.
  • Fixed that alarms related to Generator protections would remain triggered if "Delay" was set to 0.0 seconds.
  • Fixed false detection of "Engine running" due to "noisy" busbar.
  • CODESYS: Fixed that some features in libraries and on Modbus, related to alarms, were missing.
  • Fixed that "Engine ready delay" would be ignored on SGs.
  • Fixed that on the display the "Counters" screen would show irrelevant entries.
  • Fixed that alarm and status for "Voltage or frequency not OK" did not trigger/update according to the settings.
  • Fixed that status for "Voltage and frequency OK" did not respect the parameter "Delay" settings.
  • Fixed that status text "Regulator frozen" could be shown when engine was in "stopped" state.
  • Fixed that Regulator ramp up/down did not work when operating in load share mode.
  • Fixed that alarm "Earth inverse time over-current" did not trip according to the settings.
  • Fixed that the alarm "CODESYS configuration conflict" would trigger repeatedly when downloading the CODESYS application.
  • Fixed inconsistent operation of the Regulator ramp functionality.
  • Fixed that CustomLogic could stop working if the controller was power cycled immediately after "write" of a new CustomLogic configuration.
  • Fixed falsely detection of Volt/Hz due to missing data from the ACM card.
  • Fixed that inhibit functionallity was not available for NEL groups.
  • Fixed that the Regulator status screen could show wrong values.
  • Fixed that error in CustomLogic menu configuration could result in a system error (Debug.lock).
  • Fixed a potential issue with inhibits not beeing updated.
  • Fixed that "Engine start-and-close" in combination with "Blackout close" would close the breaker before the engine was running.
  • Fixed that, in "I/O Configuration", inputs of type "DI" would show as "Undefined" when used for CustomLogic.
  • Fixed that "Derate" functionallity did not influence "Power Available" calculation correctly, thus affecting load share.
  • Fixed "Status OK" handling on ACM3.2.

DU 300

New features:

  • Extended alarm information.
  • Support of ACM3.2 V.1.0.0.0.
  • Support of Trip breaker outputs.
  • Support of /IO extension unit.

Changes:

  • Version page layout.
  • Backup and restore information.

Corrections:

  • Text bug in live views.
  • DU shows random info message.
  • Display showing wrong version number.
  • ApplState not updating text.
  • Backup from the display shows undefined text in information window.
  • Missing text for View design.
  • Restore info page: Not all cards is shown.
  • Display does not update alarm and event texts, when the custom text is changed on external breaker.
  • Backup status should handle error status.
  • Possible to enter alarm sub-menus with an empty alarms list.
  • Parameter settings are shown on the display, when setting up digital outputs.

1.0.4.1

04/03/2019

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.10.0

PPU 300

Corrections:

  • BSP version 3.0.1.0 supported.
  • Negative fixed power deload dit not work. Instead of ramping to zero, it increases load.
  • AVR/GOV output selection failure alarm triggered after software upgrade.

DU 300

New features:

  • Support for multiple menu levels.
  • Display shows a pop-up window for the user before going into service mode.
  • Informs the user about development of the software.

Changes:

  • Support for PlantSupervision ver 1.0.5.0.

Corrections:

  • IOM3.4: DO's are not shown on display and in PICUS.
  • Display is not loading min. and max. from parameters when they are changed.
  • Power derate temperature is not shown on DU until power cycle.
  • When changing type, DU sometimes freezes until it restarts.
  • DU300 reboot in view designer.
  • Not able to close alarm pop-up.
  • Alarm "trigger value" is not updated if the alarm is already in the alarm list.
  • DU300 does not check versions for individual REST resources.
  • View designer cannot add counters to counters template.

1.0.4.1

19/11/2018

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.8.0

PPU 300

Corrections:

  • BSP version 3.0.1.0 supported.
  • Negative fixed power deload dit not work. Instead of ramping to zero, it increases load.
  • AVR/GOV output selection failure alarm triggered after software upgrade.

DU 300

  • No changes

1.0.4.0

06/07/2018

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.8.0

PPU 300

New features:

  • Now possible to use 16 controllers in single line

DU 300

  • No changes

1.0.3.0

20/04/2018

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.8.0

PPU 300 

New features:

  • CODESYS add-on
  • Frequency-dependent droop regulation
  • Support of GAM3.2 module with stand-alone possible
  • Able to abort "Lamp test" dialogue box
  • Power ramp configuration improved for better user experience
  • Selectable offsets for fixed P, Q and CosPhi regulation
  • Alarms made available in custom logic
  • Analogue I/O made available in custom logic
  • Parameter values made available in custom logic
  • Use external analogue signal as regulator set point
  • Alarm for F/V not OK made independent of GOV/AVR configuration
  • Power regulator set point range extended to -100 % to +100 %
  • GOV/AVR status display on PICUS and display
  • Regulation on SG 
  • Freeze regulation
  • Support of IOM3.4
  • Analogue value compare and operate function in custom logic

Changes: 

  • Optimised menu layout for better user experience
  • Improved ACM firmware update sequence

Corrections:

  • Compact breaker, optimised spring load sequence
  • "Blackout detection mismatch" functionality corrected
  • Fixed missing trip alarms
  • Manual regulation not possible with certain regulator settings
  • Fixed that "GB open-and-stop command" was ignored
  • Fixed that running detection by means of digital input could be delayed (affecting "Engine ready LED")
  • Fixed that in manual regulation mode, relay output could sometimes be left in "activated" state
  • Fixed that "Remove start" input could cause unintended short activation of crank relay
  • Fixed that cancelling a stop sequence could result in engine stopping anyway
  • Fixed that command "Open generator breaker and stop engine" could leave engine running
  • Fixed that running detection would not terminate crank timer
  • Fixed that alarms "GOV and AVR regulation error" would not be triggered
  • Alarms are always shown, even if configured as "suppressed"
  • Active start block alarm can no longer abort cooldown sequence
  • Genset temperature power derate functionality improved
  • "Start engine and close GB" command is now blocked by "Block engine start" command
  • Alarm on controller with breaker feedback error could result in breaker opening and engine stopping
  • DG suddenly becoming last controller on busbar during de-load, would trip its breaker
  • Detection of "Vector mismatch" improved
  • Fixed that "Freeze regulation" could leave relay output in "activated" state
  • Fixed that "BTB trip" command did not cancel synchronisation
  • Engine state in switchboard will now resolve to "Ready" instead of "Not Ready"

DU 300

New features:

  • Livedata configurator (View design)
  • Regulator screen (GOV/AVR)
  • Livedata dynamic reload integration
  • Message box popup

Changes:

  • Added display specific support for introspecting memory data
  • Update ID and labels on pair screen when entering the screen
  • Custom curves max precision changed from 2 to 8
  • Support for REST 1.0.4.0
  • Improvement to log output
  • Added direction to command list

Corrections:

  • DU relay not working
  • ML300 Backwards compatibility issues of DU
  • Parameter graph, special case fail
  • Livedata scales are not appearing
  • Event log was not telling which "command" (button) was pressed.
  • Blocking pop-up on DU 300 if controller software does not match.
  • Counter pop-ups now working correctly.
  • Display alarm list deadlock removed.
  • DU 300 able to change from service mode to app mode.
  • Inhibit counter on the parameters was showing wrong number of inhibits
  • Comma insted of dot between the (rack#,slot#) presentation of card name
  • Identify did not work when logged on
  • Corrections to dynamic reload of livedata
  • Corrections to eventlog navigation
  • Update value list on changes
  • Applying broadcast storm filter on startup
  • Display not showing Priority
  • Pair controller not working correctly with rework.

 

1.0.2.0

29/09/2017

New features:

  • Acces to all alarm status information from CODESYS
  • Extended status information for alarm functionblocks in CODESYS   

Changes: 

  • Software mismatch on hardware module(s) alarm only occur if first, second or third digit on IO card version is changed
  • New EIM 3.1 software 2.0.1.0

1.0.1.0

25/08/2017

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.6.0


PPU 300 

New features:
   1  - 4 directional over-current alarms have been added to BTB (ANSI 67).
   2  - 2 directional over-current alarms have been added to SC and SG (ANSI 67).
   3  - Support of lamp test function.
   4  - Support of controller identify function.
   5  - Active regulator mode will be deactivated if a new is requested.
   6  - Additional information regarding alarms, breaker-, busbar- and generator status made available on Modbus.
   7  - Added "Critical process error"" alarm.
   8  - Last DG will trip if no other feeders are closed in the plant.

Changes:
   1  - "Power supply" parameter menu renamed to "Hardware".
   2  - "Network" parameter group moved to "Hardware" instead of "Utility". 
   3  - "Reset ratio" renamed to "Hysteresis" for protection alarms.
   4  - General check that "Nominal settings" cannot be configured to 0.
   5  - "Fixed power factor" renamed to "Fixed CosPhi".
   6  - "Analog" renamed to "Analogue".
   7  - "System not OK" alarm action is changed to "Warning".
   8  - New ACM 3.1 software 4.0.1.4.
   9  - New PCM 3.1 software 2.0.0.2.
   10 - The others are version 1.0.3.0.
   11 - "Directional over-current" alarm min. and max. set points have been extended to -300 % and 300 %.
   12 - Only one regulator request is accepted if more have been received.
   13 - It is possible to configure action on "System not OK" alarm.

Corrections:
   1 - Controller types SC, SG and BTB stop synchronising if measure feedback disappears.
   2 – Regulator could freeze if regulators were used in custom logic.
   3 - Regulator continued to regulate after feedback failure on GB.


DU 300

New features:
- Implemented first part of custom stylesheets
- Curves have been added to parameters
- Lamp test
- Identify feature to communication screen
- Units change on display
                      
Changes:
- Navigation and editing in I/O input text is now possible from the keyboard
- Default live data views updated
- Edit line design has been updated
- Updated counter screen to use states
- Default text in keyboard will show resolution
- Live data screens dynamic update (step 1)
- REST version control improvement step 1 (A+B match)
- REST version control improvement step 2 (new REST resource implementation)
- Live data dial meter and vertical bar widgets improved
- Production screen changed to versions screen, production data now visible in about screen
- Added DNS possibility to communication screen
- Added IPv6 address to communication screen
- Live data using REST to build screen and widgets
- Terminal values updated to only show allowed precision
- Updated help screens
                      
Corrections:
- Custom inhibit does no longer clear other inhibit flags
- Placeholder text from previous screen does no longer influence logon screen
- Handling of empty list in pair screen
- Pair screen automatically keeps rescanning for controllers if previously connected to a controller
- Elements in parameters are represented in the same order as in the base unit
- Preparation of lists in the application improved
- Removed dot key from keyboard when value is integer, or precision is zero
- Network off pop-up did not show the first time the display lost connection
- Do not allow user to press OK in empty pair list
- Cardlist serial to be a string instead of integer
- Display reboots after setting up AVR
- No longer showing all functions when function groups is empty
- Cleaned up warnings
- Not able to enable/disable the alarm "Ethernet redundancy broken"

1.0.0.3

12/04/2017

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.5.0

 

PPU 300

Corrections:
   1- Trip and stop action did not stop the engine in switchboard mode 
   2- Customlogic inputs was evaluated wrong in scan
   3- Sync. type was changed back from Static to dynamic after a power cycle

DU 300

No changes

1.0.0.2

14/03/2017

Corrections:

  • Start and close command now works correctly if “Voltage and frequency OK” timer has been increased.
  • Open and stop command can also stop the engine if breaker is opened, when command has been sent.

1.0.0.0

21/12/2016

PPU 300: Initial release

DU 300 ver. 1.0.5.0:

New features:

  • Added placeholder text when the label is completly empty, when you enter an I/O name, the current name of the IO will be shown.
  • Support of 4 line pop-up in the display.
  • Displays the variant on the info/about screen.
  • New pair feature (select base unit).

Changes:

  • DU registration of 4 new languages.
  • DU REST 1.0.2.0 support.
  • Update DU help files.
  • Added REST version to "About screen" in row 3.
  • Made it possible to take pictures of the first pair screen

Corrections:

  • Changed home screen Alarm 8000002 to Alarms 800025 to match the path.
  • Removed two arrows that were shown in parameter groups that was not supposed to be there.
  • Display could have problems, connecting to base units if it was connected in a daisy chain.
  • Making the algorithm responsible for showing/hiding pop-up windows.
  • Updating status text, and diodes in DU is made faster.
  • Crash in start-up sequence removed.
  • Corrected some filtering of allowed functions.
  • Remove illegal references to parameters.
  • Incorrect text shown when valueList had less than 2 elements removed.
  • If alarm screen is detected in the screen history, the current screen is rewound to that alarm screen.
  • DU updating speed improved.
  • Pop-up header characters clip adjusted.
  • IO scale: impossible to select a custom scale with only 1 point.
  • Header text initialised.
  • Pairing pop-up cuts of text on very long labels.
  • Controller for selecting base unit.
  • Appending empty unit to analogue output functions not possible.
  • DU start-up screen has been corrected.
  • Label corrected to "Restart" display instead of "Reset".

On this page, you can download software updates for your product(s) and help yourself to various utility tools and add-ons that will assist you in setting up, detecting faults and configuring your product(s).

Please be advised that not all of our products can be updated by the user. Nor do all of our products come with a utility tool. Consequently, the list on this page cannot be considered an overview of our product programme.

DEIF will register your download along with the used e-mail address for the purpose of sending out information on future updates, if requested.

DEIF cannot be made responsible for any consequences of failed product updates or use of utility tools. Nor can DEIF A/S be made responsible for consequences of changes in behaviour of products due to a software upgrade. It is always the responsibility of the user to ensure correct set-up and configuration before commissioning. Please study the version log of the software before updating the product.

Licence agreement for software downloaded from www.deif.com

Downloaded software remains the property of DEIF. The software may not be distributed for commercial purposes, changed or reused in full or in part or sold to any third parties.

The latest versions for full functionality

As always, we recommend that you install our offered improvements to fully utilise your DEIF product.

All improved software can be downloaded at your convenience at www.deif.com under “Software”.

Should you have any questions or experience problems finding the relevant software for your product, please feel free to call DEIF A/S at +45 96149614 or your relevant local DEIF office. Alternatively, we are always ready to assist you, if you send an e-mail to support@deif.com.