Multi-line 300 GPC 300 ver. 1.x.x.

Multi-line 300 GPC 300 ver. 1.x.x.

You have chosen to download our software.

Within a few seconds, you will receive an email containing a download link.

Having trouble using the software? Please contact support@deif.com. 

Best regards, 

DEIF A/S

The software is subject to copyright DEIF A/S
By following the above mentioned link and downloading the file you automatically accept DEIF A/S copyright and license agreement (EULA). The license agreement can be found on www.deif.com/software

1.0.27.0

This software package consist of:

  • Multi-line 300, GPC 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.20.0

GPC 300

New feature:

• Two new alarms added:
1) "DEIF network has only one connection"
    Default: enabled, Auto ack, No latch (all configurable)
    Action: Warning (hidden)
    Menu location: Communication->DEIF network->
   
       Will trigger when going from 2 to 1 connection are detected.
    - Zero connections is valid for a stand-alone setup.
    - Zero connections will trigger missing all controllers in a system setup.
2) "DEIF network fork detected"
    Default: enabled, Auto ack, No latch (all editable)
    Action: Warning (hidden)
    Menu location: Communication->DEIF network->
    Will trigger when 3 or more connections are detected.

Corrections:

• Fixed issue where the ROCOF set point and triggered value were not shown on the alarm page (DU300 and PICUS).
• Fixed issue where "Data loss on DEIF network" would incorrectly trigger at start-up.
• Fixed issue where a redundancy supervision alarm did not trigger when external network equipment was used.
• Increased number of missing controller alarms shown.
• Fixed issue with controller crashing doing backup.
• Fixed issue where a controller performed an unwanted restart due to rare issue in Modbus.
• Fixed issue where reading IO status on Modbus could cause unwanted restart of the application software.

 

1.0.23.0

08/03/2023

This software package consist of:

  • Multi-line 300, GPC 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.20.0

GPC 300

New feature:

  • New variant that has a mains with mains breaker and tie breaker.
  • Added emulation for single gensets.
  • Added the possibility to read dynamic section status in CODESYS.
  • Added PMS power measurement data.

Changes:

  • Changed the maximum value for breaker open failure delay to 60 seconds.
  • Changed the maximum value for breaker close failure delay to 60 seconds.
  • Added PMS power measurement data.
  • Selection of "Phase-Phase" / "Phase-Neutral" on selected voltage protections are always shown.

Corrections:

  • Emulation now works with fixed power, while mains is exporting (negative kW values on mains).
  • Breaker operation counter now increments correctly in emulation.
  • Fixed issue with no tags shown in HMI for AC setup parameter.
  • Improved backup percentage count in PICUS.
  • Missing texts have been added.
  • It is now possible to access the DM2 log from PICUS.
  • Fixed missing IOM3.4 support.
  • Analogue AVR now works in emulation.
  • Fixed an issue with external breaker feature in emulation.
  • Fixed an issue with using the stop command from switchboard in emulation. This would not stop the engine when running in parallel.
  • Mains variants have regulator control available in emulation.
  • Close failure can now be emulated.
  • The response time for the trip breaker output can exceed 100ms if the configuration has been done in a particular order and the controller has not been power cycled.
  • Fixed issue where there could be Hz on the generator measurements in emulation when the engine was stopped.
  • Fixed issue with MPU wire break. It is now working.
  • Fixed issue where the states in emulation were preserved when emulation was not enabled.

DU 300

New features:

  • Introduces a new view for exhaust after-treatment dashboard increasing the support of Tier 4 and Stage V engines.

1.0.21.0

07/10/2022

This software package consist of:

  • Multi-line 300, GPC 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.19.0

GPC 300

New feature:

  • Added support for multiple applications with a parameter to select active application and custom plant name. (Not supported by PICUS.)

Corrections:

  • Fixed issue where I/O parameter configuration was passed on from one external breaker or a heavy consumer on the single line to another when during commissioning. I/O configuration and parameters are not reset.
  • Fixed issue where manual regulation didn't work in emulation.
  • Fixed issue where analogue regulation was unstable in emulation.
  • Fixed issue with GAM3.2 not working in emulation.
  • Fixed issue with incorrect regulator mode when a single genset (GB only) connected to mains.
  • Actual Power total in % is now showing on DU-300 (Live data) and in PICUS.
  • Fixed issue with external voltage offset in load sharing not working.

DU 300

New features:

  • Introduces a new view for exhaust after-treatment dashboard increasing the support of Tier 4 and Stage V engines.

1.0.20.0

09/09/2022

This software package consist of:

  • Multi-line 300, GPC 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.19.0

GPC 300

First release

DU 300

New features:

  • Introduces a new view for exhaust after-treatment dashboard increasing the support of Tier 4 and Stage V engines.

On this page, you can download software updates for your product(s) and help yourself to various utility tools and add-ons that will assist you in setting up, detecting faults and configuring your product(s).

Please be advised that not all of our products can be updated by the user. Nor do all of our products come with a utility tool. Consequently, the list on this page cannot be considered an overview of our product programme.

DEIF will register your download along with the used e-mail address for the purpose of sending out information on future updates, if requested.

DEIF cannot be made responsible for any consequences of failed product updates or use of utility tools. Nor can DEIF A/S be made responsible for consequences of changes in behaviour of products due to a software upgrade. It is always the responsibility of the user to ensure correct set-up and configuration before commissioning. Please study the version log of the software before updating the product.

Licence agreement for software downloaded from www.deif.com

Downloaded software remains the property of DEIF. The software may not be distributed for commercial purposes, changed or reused in full or in part or sold to any third parties.

The latest versions for full functionality

As always, we recommend that you install our offered improvements to fully utilise your DEIF product.

All improved software can be downloaded at your convenience at www.deif.com under “Software”.

Should you have any questions or experience problems finding the relevant software for your product, please feel free to call DEIF A/S at +45 96149614 or your relevant local DEIF office. Alternatively, we are always ready to assist you, if you send an e-mail to support@deif.com.