Select your business area

We use this information to provide content associated with segment of your choice.
You can change your selection any time.

Multi-line 2 ALC Application Software series 4x

Ce logiciel concerne les produits DEIF suivants :

Vous allez télécharger 4.11.0

Les principales modifications depuis la dernière version sont les suivantes:

PM compatibility version 1.16.0
Includes version 1.15.0

New features:

  •    Now possible to open and close LG's while position failure is present.
  •    Block LG fail classes added
          • Position failure alarms set default to LG Block fail class.

Corrections:

  •    Corrected ALC Breaker Feedback Emulation.
 

Ver. Date Description

4.11.0

13/02/2020

PM compatibility version 1.16.0
Includes version 1.15.0

New features:

  •    Now possible to open and close LG's while position failure is present.
  •    Block LG fail classes added
          • Position failure alarms set default to LG Block fail class.

Corrections:

  •    Corrected ALC Breaker Feedback Emulation.
 

4.10.1

10/01/2020

PM compatibility version 1.16.0

Corrections:

  •    Horn relay now working
  •    M-Logic PMS flags for GB/MB closed now working 
  •    LG(load group) pos. fail alarm now possible when LG is disabled

4.10.0

12/12/2019

PM compatibility version 1.16.0

Features:

  •    32 DG/Mains support
          • Support of 32 DG's in ID range 1-32 (AGC-4/200, version 4.65.0 required).
          • Support of 32 Mains in ID range 1-32 (AGC-4/200, version 4.65.0 required).
          • Support of 16 ASC's in ID range 25-40 (ASC-4, version 4.06.0 required).
          • Support of  8 ALC's in ID range 25-40.
  •    Support of ASC PV and Battery.
  •    Heavy Consumer logic added.
  •    Flip/Flops added to M-logic.

Changes:

  •    Disconnect Load can now be set to 200 % and 999 sec.

Corrections:

  •    Corrected: Tripped open relay hanging on redundant unit.
  •    Corrected: LG's are not opened in AUTO mode when disabled.
  •    Corrected: Digital input alarms are not activated by input.

4.00.1

29/01/2018

Corrections:

  • In some instances, all fail classes were initialised to "Shutdown" unintentionally.

4.00.0

30/10/2017

PM compatibility version 1.15.0
  
Features:
1- Includable in Power Management application type "Standard" together with AGC-4 and AGC 200.
a) Up to 16 gensets.
  b) Up to 16 mains.
c) Up to 8 BTBs/ALCs in plants.
d) Spinning reserve support.
2- Able to close and open breakers according to available power from DG. 
3- Able to place the ALC in mains load point.  