iE150 Application SW
iE150 Application SW
You have chosen to download our software.
Within a few seconds, you will receive an email containing a download link.
Having trouble using the software? Please contact support@deif.com.
Best regards,
DEIF A/S
The software is subject to copyright DEIF A/S
By following the above mentioned link and downloading the file you automatically accept DEIF A/S copyright and license agreement (EULA). The license agreement can be found on www.deif.com/software
1.32.0
- USW version required: 3.62.1
- TDU version required: 1.4.5.0
PM compatibility: 1.41.0
New features
- STORAGE: Added new protocol, Kehua Tech Local Controller (KC541A)
- STORAGE: Added Faro BCU protocol.
- STORAGE: Added new BMS protocol "CATL EnerOne Plus"; renamed "CATL liquid cooled" to "CATL EnerOne".
- STORAGE: Added a new parameter 17056 "SOC resolution" to allow changing the default resolution for SOC of 1% to 0.1% or 0.01%.
- STORAGE: Added CubEnergy BCU and Lithion GB protocol.
- EIC: Added fuel rate alarm based on active power.
- EIC: Added Guascor GCS-e ECU protocol.
- EIC: Added aftertreatment icons for ISUZU.
- EIC: Added Volvo Penta D12 protocol.
- GENSET: Added counter for a number of successful generator starts.
- GENSET: Add support of digital load sharing with SmartGen in SEMI mode.
Changes
- STORAGE: Renamed ESS protocol for Yingbo PCS to InPower PCS.
- EIC: Added TSC1 to YC-ECU-A.
- EIC: Updated crankcase pressure (SPN 101) to kPa unit in delta alarms.
- EIC: Updated Cummins PGI to version 4.
Corrections
- STORAGE: Fixed an issue where single controller in AMF would charge from Mains when energy functionality was OK and "SOC + plant assist charging" was used as Mains charging mode.
- STORAGE: Fixed an issue for Sungrow LC300 where heartbeat was not working.
- STORAGE: Fixed several issues for WEG BIW610 PCS and WEG BMS:
- WEG BIW610 PCS registers which were interpreted as big endian are now interpreted as little endian byteswap.
- WEG BIW610 PCS sends nominal voltage/frequency on registers 500 and 508.
- WEG BIW610 PCS will only send start signal when PCS is in the "Waiting" state.
- WEG BMS sends a pulse every 90 s to register 95 for connecting BMS clusters.
- WEG BMS will trigger BMS warning on every 'minor' alarm register with function code 0x02 and BMS shutdown on every 'moderate' alarm register with function code 0x02.
- STORAGE/SOLAR: Fixed inaccessible menus in tree and parameter views on display.
- STORAGE/SOLAR/DGHYBRID: Corrected scaling of active power set point with non-default parameter 9030.
- Configured Droop curve 2 with power factor output, now functions correctly.
- STORAGE/SOLAR: Prevented mix-up of readings when using multiple powermeter types.
1.32.0 |
04/06/2025 |
PM compatibility: 1.41.0 New features
Changes
Corrections
|
1.31.0 |
05/05/2025 |
PM compatibility: 1.41.0 New features
Changes
Corrections
|